Section 19
Technical data
19.1
Dimensions
Table 552:
Dimensions of the IED - 3U full 19" rack
Description
Value
Width
17.48 inches (444 mm)
Height
5.20 inches (132 mm), 3U
Depth
9.82 inches (249.5 mm)
Weight box
<22.04 lbs (10 kg)
19.2
Power supply
Table 553:
Power supply
Description
600PSM01
600PSM02
600PSM03
V
n
24, 30 V DC
48, 60, 110, 125 V DC
100, 110, 120, 220, 240
V AC, 50 and 60 Hz
110, 125, 220, 250 V DC
V
n
variation
80...120% of V
n
(24...30
V DC)
80...120% of V
n
(38.4...150 V DC)
85...110% of V
n
(85...264 V AC)
80...120% of V
n
(88...300 V DC)
Maximum load of
auxiliary voltage supply
35 W for DC
40 VA for AC
Ripple in the DC auxiliary
voltage
Max 15% of the DC value (at frequency of 100 and 120 Hz)
Maximum interruption
time in the auxiliary DC
voltage without resetting
the IED
50 ms at V
n
Resolution of the voltage
measurement in PSM
module
1 bit represents 0,5 V
(+/- 1 VDC)
1 bit represents 1 V (+/-
1 VDC)
1 bit represents 2 V (+/-
1 VDC)
1MRK 502 048-UUS A
Section 19
Technical data
723
Technical manual