
Table 74:
OOSPPAM (78) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
Groups
ForwardR
0.00 - 1000.00
% Zb
0.01
1.00
Real part of total forward impedance for Z2, in
% of VBase/(sqrt(3)*IBase)
ForwardX
0.00 - 1000.00
% Zb
0.01
10.00
Imag. part of total forward impedance for Z2, in
% of VBase/(sqrt(3)*IBase)
InvertCTCurr
No
Yes
-
-
No
Invert current direction
ReverseR
0.00 - 1000.00
% Zb
0.01
1.00
Real part of source impedance behind relay, in
% of VBase/(sqrt(3)*IBase)
ReverseX
0.00 - 1000.00
% Zb
0.01
10.00
Imag. part of source impedance behind relay,
in % of VBase/(sqrt(3)*IBase)
Table 75:
OOSPPAM (78) Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
StartAngle
90.0 - 130.0
Deg
0.1
110.0
Angle between two rotors to get the pick up
signal, in deg
TripAngle
15.0 - 90.0
Deg
0.1
60.0
Maximum rotor angle to allow trip signals, in
deg
7.4.6
Monitored data
Table 76:
OOSPPAM (78) Monitored data
Name
Type
Values (Range)
Unit
Description
VOLTAGE
REAL
-
kV
Magnitude of the measured
positive-sequence voltage, in
V
CURRENT
REAL
-
A
Magnitude of the measured
positive-sequence current, in
A
R
REAL
-
%
Real part of measured
positive-sequence impedance
% of VBase/(sqrt(3)*IBase)
X
REAL
-
%
Imaginary part of measured
positive-seq impedance % of
VBase/(sqrt(3)*IBase)
ROTORANG
REAL
-
deg
Rotor angle as estimated by
the out-of-step function
UCOSPHI
REAL
-
kV
Estimated Ucos(Phi) voltage
during pole slip, in V
Section 7
1MRK 502 048-UUS A
Impedance protection
176
Technical manual