Name
Type
Description
PICKUP1
BOOLEAN
Pickup signal from stage 1
PICKUP2
BOOLEAN
Pickup signal from stage 2
P
REAL
Active Power
PPERCENT
REAL
Active power in % of calculated power base value
Q
REAL
Reactive power
QPERCENT
REAL
Reactive power in % of calculated power base value
8.7.3.4
Settings
Table 129:
GUPPDUP (37) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
OpMode1
Disabled
UnderPower
-
-
UnderPower
Operation mode 1
Power1
0.0 - 500.0
%
0.1
1.0
Power setting for stage 1 in % of calculated
power base value
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 1
TripDelay1
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 1
OpMode2
Disabled
UnderPower
-
-
UnderPower
Operation mode 2
Power2
0.0 - 500.0
%
0.1
1.0
Power setting for stage 2 in % of calculated
power base value
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 2
TripDelay2
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 2
Table 130:
GUPPDUP (37) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
TD
0.00 - 0.99
-
0.01
0.00
Low pass filter coefficient for power
measurement, V and I
1MRK 502 048-UUS A
Section 8
Current protection
257