Name
Values (Range)
Unit
Step
Default
Description
Power2
0.0 - 500.0
%
0.1
1.0
Power setting for stage 2 in % of calculated
power base value
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 2
TripDelay2
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 2
Table 124:
GOPPDOP (32) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
k
0.00 - 0.99
-
0.01
0.00
Low pass filter coefficient for power
measurement, V and I
Table 125:
GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Mode of measurement for current and voltage
8.7.2.5
Monitored data
Table 126:
GOPPDOP (32) Monitored data
Name
Type
Values (Range)
Unit
Description
P
REAL
-
MW
Active Power
PPERCENT
REAL
-
%
Active power in % of
calculated power base value
Q
REAL
-
MVAr
Reactive power
QPERCENT
REAL
-
%
Reactive power in % of
calculated power base value
8.7.3
Directional underpower protection GUPPDUP (37)
1MRK 502 048-UUS A
Section 8
Current protection
255
Technical manual