Name
Type
Description
VP289TR
BOOLEAN
Switch status of 289 is valid (open or closed)
VP789TR
BOOLEAN
Switch status of 789 is valid (open or closed)
VP1289TR
BOOLEAN
Switch status of 189 and 289 are valid (open or closed)
12.3.9.6
Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
12.3.10
Interlocking for transformer bay AB_TRAFO (3)
12.3.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for transformer bay
AB_TRAFO
-
3
12.3.10.2
Functionality
The interlocking for transformer bay (AB_TRAFO, 3) function is used for a transformer
bay connected to a double busbar arrangement according to figure
used when there is no disconnector between circuit breaker and transformer. Otherwise,
the interlocking for line bay (ABC_LINE, 3) function can be used. This function can also
be used in single busbar arrangements.
Section 12
1MRK 502 048-UUS A
Control
436
Technical manual