Table 59. Disturbance recorder DRPRDRE
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and
maximum number of channels, typical value)
340 seconds (100 recordings) at
50 Hz
280 seconds (80 recordings) at 60
Hz
Table 60. Station battery supervision SPVNZBAT
Function
Range or value
Accuracy
Lower limit for the battery
terminal voltage
(60-140) % of Vbat
± 1.0% of set battery voltage
Reset ratio, lower limit
<105 %
-
Upper limit for the battery
terminal voltage
(60-140) % of Vbat
± 1.0% of set battery voltage
Reset ratio, upper limit
>95 %
-
Timers
(0.000-60.000) s
± 0.5% ± 110 ms
Table 61. Insulation gas monitoring function SSIMG (63)
Function
Range or value
Accuracy
Pressure alarm
0.00-25.00
-
Pressure lockout
0.00-25.00
-
Temperature alarm
-40.00-200.00
-
Temperature lockout
-40.00-200.00
-
Timers
(0.000-60.000) s
± 0.5% ± 110 ms
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011
ABB
77