Voltage protection
Table 36. Two step undervoltage protection UV2PTUV (27)
Function
Range or value
Accuracy
Operate voltage, low and high
step
(1–100)% of
VBase
± 0.5% of V
n
Reset ratio
<105%
-
Inverse time characteristics for
low and high step, see table
-
See table
Definite time delay, step 1
(0.00 - 6000.00) s
± 0.5% ± 25 ms
Definite time delays, step 2
(0.000-60.000) s
± 0.5% ±25 ms
Minimum operate time, inverse
characteristics
(0.000–60.000) s
± 0.5% ± 25 ms
Operate time, pickup function
30 ms typically at 2 to 0.5 x V
set
-
Reset time, pickup function
40 ms typically at 0.5 to 2 x V
set
-
Critical impulse time
10 ms typically at 2 to 0 x V
set
-
Impulse margin time
15 ms typically
-