Table 38. Two step residual overvoltage protection ROV2PTOV (59N)
Function
Range or value
Accuracy
Operate voltage, step 1
(1-200)% of
VBase
± 0.5% of V
n
at V < V
n
± 0.5% of V at V > V
n
Operate voltage, step 2
(1–100)% of
VBase
± 0.5% of V
n
at V < V
n
± 0.5% of V at V > V
n
Reset ratio
>95%
-
Inverse time characteristics for
low and high step, see table
-
See table
Definite time setting, step 1
(0.00–6000.00) s
± 0.5% ± 25 ms
Definite time setting, step 2
(0.000–60.000) s
± 0.5% ± 25 ms
Minimum operate time for step 1
inverse characteristic
(0.000-60.000) s
± 0.5% ± 25 ms
Operate time, pickup function
30 ms typically at 0 to 2 x V
set
-
Reset time, pickup function
40 ms typically at 2 to 0 x V
set
-
Critical impulse time
10 ms typically at 0 to 2 x V
set
-
Impulse margin time
15 ms typically
-
Table 39. Loss of voltage check LOVPTUV (27)
Function
Range or value
Accuracy
Operate voltage
(0–100)% of VBase
± 0.5% of V
n
Reset ratio
<105%
-
Pulse timer
(0.050–60.000) s
± 0.5% ± 25 ms
Timers
(0.000–60.000) s
± 0.5% ± 25 ms
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011