Table 45. Breaker close/trip circuit monitoring TCSSCBR
Function
Range or value
Accuracy
Operate time delay
(0.020 - 300.000) s
± 0,5% ± 110 ms
Control
Table 46. Synchronizing, synchronism check and energizing check SESRSYN (25)
Function
Range or value
Accuracy
Phase shift,
j
line
-
j
bus
(-180 to 180) degrees
-
Voltage ratio, V
bus
/V
line
0.2 to 5.0
-
Frequency difference limit between bus
and line
(0.003-1.000) Hz
± 2.0 mHz
Phase angle difference limit between
bus and line
(5.0-90.0) degrees
± 2.0 degrees
Voltage difference limit between bus
and line
± 0.5% of V
n
Time delay output for synchronism
check
(0.000-60.000) s
± 0.5% ± 25 ms
Time delay for energizing check
(0.000-60.000) s
± 0.5% ± 25 ms
Closing time for the circuit breaker
(0.000-60.000) s
± 0.5% ± 25 ms
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011