Table 48. Autorecloser STBRREC (79)
Function
Range or value
Accuracy
Number of autoreclosing shots 1-5
-
Autoreclosing open time: Shot
1 - t1 3Ph
Shot 1 - t1 1Ph
(0.000-60.000) s
± 0.5% ± 25 ms
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
(0.00-6000.00) s
Autorecloser maximum wait
time for sync
(0.00-6000.00) s
Open time extension for long
trip time
(0.000-60.000) s
Maximum trip pulse duration
(0.000-60.000) s
Inhibit reset time
(0.000-60.000) s
Reset time
(0.00-6000.00) s
Minimum time CB must be
closed before AR becomes
ready for autoreclosing cycle
(0.00-6000.00) s
CB check time before
unsuccessful
(0.00-6000.00) s
Wait for master release
(0.00-6000.00) s
Wait time after close
command before proceeding
to next shot
(0.000-60.000) s
Logic
Table 49. Tripping logic SMPPTRC (94)
Function
Range or value
Accuracy
Trip action
3-ph
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011
72