Table 24. Four step phase overcurrent protection OC4SPTOC (51_67)
Function
Setting range
Accuracy
Operate current
(5-2500)% of
lBase
±
1.0% of I
n
at I
£
I
n
±
1.0% of I at I > I
n
Reset ratio
> 95%
-
Min. operating current
(1-10000)% of
lBase
±
1.0% of I
n
at I < I
n
±
1.0% of I at I > I
n
Independent time delay
(0.000-60.000) s
±
0.5%
±
25 ms
Minimum operate time
for inverse characteristics
(0.000-60.000) s
±
0.5%
±
25 ms
Inverse characteristics,
see table
17 curve types
See table
and
table
Operate time,
nondirectionalpickup
function
20 ms typically at 0 to 2 x I
set
-
Reset time, pickup
function
30 ms typically at 2 to 0 x I
set
-
Operate time, directional
pickup function
30 ms typically at 0 to 2 x I
set
-
Reset time, directional
pickup function
25 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011