Trip matrix logic TMAGGIO
Trip matrix logic TMAGGIO function is used to
route trip signals and other logical output
signals to different output contacts on the IED.
TMAGGIO output signals and the physical
outputs allows the user to adapt the signals to
the physical tripping outputs according to the
specific application needs.
Configurable logic blocks
A number of logic blocks and timers are
available for the user to adapt the configuration
to the specific application needs.
•
OR
function block.
•
INVERTER
function blocks that inverts the
input signal.
•
PULSETIMER
function block can be used,
for example, for pulse extensions or limiting
of operation of outputs.
•
GATE
function block is used for whether or
not a signal should be able to pass from the
input to the output.
•
XOR
function block.
•
LOOPDELAY
function block used to delay
the output signal one execution cycle.
•
TIMERSET
function has pick-up and drop-
out delayed outputs related to the input
signal. The timer has a settable time delay.
•
AND
function block.
•
SRMEMORY
function block is a flip-flop that
can set or reset an output from two inputs
respectively. Each block has two outputs
where one is inverted. The memory setting
controls if the block's output should reset or
return to the state it was, after a power
interruption.
•
RSMEMORY
function block is a flip-flop that
can reset or set an output from two inputs
respectively. Each block has two outputs
where one is inverted. The memory setting
controls if the block's output should reset or
return to the state it was, after a power
interruption. Reset input has priority.
Boolean 16 to Integer conversion
B16I
Boolean 16 to integer conversion function
(B16I) is used to transform a set of 16 binary
(logical) signals into an integer.
Boolean 16 to Integer conversion
with logic node representation
B16IFCVI
Boolean 16 to integer conversion with logic
node representation function (B16IFCVI) is
used to transform a set of 16 binary (logical)
signals into an integer.
Integer to Boolean 16 conversion
IB16A
Integer to boolean 16 conversion function
(IB16A) is used to transform an integer into a
set of 16 binary (logical) signals.
Integer to Boolean 16 conversion
with logic node representation
IB16FCVB
Integer to boolean conversion with logic node
representation function (IB16FCVB) is used to
transform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote values
over IEC61850 depending on the operator
position input (PSTO).
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011
ABB
23