Table 42. Rate-of-change frequency protection SAPFRC (81)

Function

Range or value

Accuracy

Operate value, pickup function

(-10.00-10.00) Hz/s

± 10.0 mHz/s

Operate value, restore enable frequency (45.00 - 65.00) Hz

± 2.0 mHz

Timers

(0.000 - 60.000) s

<130 ms

Operate time, pickup function

At 50 Hz: 100 ms typically
At 60 Hz: 80 ms typically

-

Secondary system supervision

Table 43. Current circuit supervision CCSRDIF (87)

Function

Range or value

Accuracy

Operate current

(5-200)% of I

n

±

 10.0% of I

n

 at I 

£

 I

n

±

 10.0% of I at I > I

n

Block current

(5-500)% of I

n

±

 5.0% of I

n

 at I 

£

 I

n

±

 5.0% of I at I > I

n

Table 44. Fuse failure supervision SDDRFUF

Function

Range or value

Accuracy

Operate voltage, zero sequence

(1-100)% of VBase

± 1.0% of V

n

Operate current, zero sequence

(1–100)% of IBase

± 1.0% of I

n

Operate voltage, negative
sequence

(1–100)% of VBase

± 0.5% of V

n

Operate current, negative
sequence

(1–100)% of IBase

± 1.0% of I

n

Operate voltage change pickup

(1–100)% of VBase

± 5.0% of V

n

Operate current change pickup

(1–100)% of IBase

± 5.0% of I

n

Operate phase voltage

(1-100)% of VBase

± 0.5% of U

n

Operate phase current

(1-100)% of IBase

± 1.0% of I

n

Operate phase dead line voltage

(1-100)% of VBase

± 0.5% of U

n

Operate phase dead line current

(1-100)% of IBase

± 1.0% of I

n

Breaker protection REQ650 ANSI

1MRK 505 269-BUS -

Product version: 1.1

Issued: April 2011

ABB

69

Summary of Contents for Relion REQ650

Page 1: ...Relion 650 series Breaker protection REQ650 ANSI Product Guide...

Page 2: ...echnical data 42 18 Ordering 84 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB ABB AB assumes no responsibility f...

Page 3: ...rocheck and energizing check functions of REQ650 provides an optimized stand alone product This IED also enables well structured and reliable protection and control systems especially in systems where...

Page 4: ...Meter CV MMXN Meter CC RPLD 52PD DRP RDRE Mont V MMXU Meter IEC61850 ANSI IEC Function Enabled in Settings DNP ANSI IEC Function Disabled in Settings 132 kV Bus 1000 1 132kV 110V 132kV 110V OC4 PTOC...

Page 5: ...D V MMXU Meter OV2 PTOV 59 3U V MMXU Meter V MSQI Meter TCS SCBR Cond SPVN ZBAT Cond Other configured functions DRP RDRE Mont IEC61850 ANSI IEC Function Enabled in Settings ANSI11000143_1_en vsd TCS S...

Page 6: ...U Meter OV2 PTOV 59 3U V MMXU Meter V MSQI Meter TCS SCBR Cond SPVN ZBAT Cond Other configured functions DRP RDRE Mont IEC61850 ANSI IEC Function Enabled in Settings ANSI11000144_1_en vsd TCS SCBR Con...

Page 7: ...3 Available functions Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1 1 Issued April 2011 ABB 7...

Page 8: ...1 EF4PTOC 51N 67N Four step directional residual overcurrent protection 1 1 1 SDEPSDE 67N Sensitive directional residual overcurrent and power protection 1 1 1 LPTTR 26 Thermal overload protection one...

Page 9: ...1 1 1 OV2PTOV 59 Two step overvoltage protection 1 1 1 ROV2PTOV 59N Two step residual overvoltage protection 1 1 1 LOVPTUV 27 Loss of voltage check 1 1 1 Frequency protection SAPTUF 81 Underfrequency...

Page 10: ...O Logic Rotating Switch for function selection and LHMI presentation 15 15 15 VSGGIO Selector mini switch extension 20 20 20 DPGGIO IEC 61850 generic communication I O functions double point 16 16 16...

Page 11: ...able logic blocks OR gate 283 283 283 INVERTER Configurable logic blocks Inverter gate 140 140 140 PULSETIMER Configurable logic blocks Pulse timer 40 40 40 GATE Configurable logic blocks Controllable...

Page 12: ...urements 6 6 6 CMMXU Phase current measurement 10 10 10 VMMXU Phase phase voltage measurement 6 6 6 CMSQI Current sequence component measurement 6 6 6 VMSQI Voltage sequence measurement 6 6 6 VNMMXU P...

Page 13: ...SUSR Measurands user defined signals for IEC60870 5 103 3 3 3 I103AR Function status auto recloser for IEC60870 5 103 1 1 1 I103EF Function status ground fault for IEC60870 5 103 1 1 1 I103FLTPROT Fun...

Page 14: ...mmunication via ST 1 1 1 GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59 59 59 GOOSEBINRCV GOOSE binary receive 4 4 4 GOOSEDPRCV GOOSE function block to receive a double point val...

Page 15: ...g groups 1 TESTMODE Test mode functionality 1 CHNGLCK Change lock function 1 TERMINALID IED identifiers 1 PRODINF Product information 1 PRIMVAL Primary system values 1 SMAI_20_1 12 Signal matrix for a...

Page 16: ...th memory The function can be set to be directional or non directional independently for each of the steps Instantaneous residual overcurrent protection EFPIOC 50N The Instantaneous residual overcurre...

Page 17: ...r is small Breaker failure protection CCRBRF 50BF current criteria can be fulfilled by one or two phase currents or one phase current plus residual current When those currents exceed the user defined...

Page 18: ...en conductors Directional over underpower protection GOPPDOP GUPPDUP 32 37 The directional over under power protection GOPPDOP 32 GUPPDUP 37 can be used wherever a high low active reactive or apparent...

Page 19: ...neutral point voltage transformer ROV2PTOV 59N has two voltage steps where step 1 can be set as inverse or definite time delayed Step 2 is always definite time delayed Loss of voltage check LOVPTUV 27...

Page 20: ...in the secondary circuits between the voltage transformer and the IED in order to avoid unwanted operations that otherwise might occur The fuse failure supervision function basically has three differe...

Page 21: ...to be connected It is used for slip frequencies that are larger than those for synchronism check and lower than a set maximum level for the synchronizing function Autorecloser SMBRREC 79 The autoreclo...

Page 22: ...ingle point generic control 8 signals SPC8GGIO The Single point generic control 8 signals SPC8GGIO function block is a collection of 8 single point commands designed to bring in commands from REMOTE S...

Page 23: ...ory setting controls if the block s output should reset or return to the state it was after a power interruption RSMEMORY function block is a flip flop that can reset or set an output from two inputs...

Page 24: ...BDR function blocks which are set to trigger the disturbance recorder All signals from start of pre fault time to the end of post fault time will be included in the recording Every disturbance report...

Page 25: ...g and after a disturbance Recorded information is used for different purposes in the short perspective for example corrective actions and long perspective for example functional analysis The Disturban...

Page 26: ...monitoring function SSCBR is used to monitor different parameters of the circuit breaker The breaker requires maintenance when the number of operations has reached a predefined value For proper funct...

Page 27: ...ble label All LEDs are configurable from the PCM600 tool Liquid crystal display LCD Keypad with push buttons for control and navigation purposes switch for selection between local and remote control a...

Page 28: ...plete The purpose is to block inadvertent IED configuration changes beyond a certain point in time Authority status ATHSTAT Authority status ATHSTAT function is an indication function block for user l...

Page 29: ...upports IEC 60870 5 103 time synchronization methods with a time stamping resolution of 5 ms Table 1 Supported communication interface and protocol alternatives Interfaces Protocols Ethernet 100BASE F...

Page 30: ...kit Flush mounting kit 19 dual rack mounting kit See ordering for details about available mounting alternatives Flush mounting the IED H I K J C F G B A E D IEC09000672 ai IEC09000672 V1 EN Figure 5...

Page 31: ...mm C 13 mm Rack mounting the IED A C B E D IEC09000676 ai IEC09000676 V1 EN Figure 7 Rack mounted IED A 224 mm 12 mm with ring lug connector B 25 5 mm C 482 6 mm 19 D 265 9 mm 6U E 13 mm Breaker prote...

Page 32: ...G B A E D IEC09000678 ai IEC09000678 V1 EN Figure 9 Wall mounting the IED A 270 mm E 190 5 mm B 252 5 mm F 296 mm C 6 8 mm G 13 mm D 268 9 mm GUID 5C185EAC 13D0 40BD 8511 58CA53EFF7DE V1 EN Figure 10...

Page 33: ...tion diagrams 1MRK006502 LB 2 PG 1 1 ANSI V1 EN Figure 11 Designation for 6U 1 2x19 casing with 1 TRM A01A A11A B11A Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1 1 Issued April 20...

Page 34: ...RK006502 LB 3 PG 1 1 ANSI V1 EN Figure 12 Communication module COM 1MRK006502 LB 4 PG 1 1 ANSI V1 EN Figure 13 Power supply module PSM 48 125V DC Breaker protection REQ650 ANSI 1MRK 505 269 BUS Produc...

Page 35: ...1 ANSI V1 EN Figure 14 Power supply module PSM 110 250V DC 1MRK006502 LB 6 PG 1 1 ANSI V1 EN Figure 15 Transformer module TRM Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1 1 Issue...

Page 36: ...nary input output BIO option Terminal X321 X324 Connection diagrams for REQ650 A11A 1MRK006502 RB 3 PG 1 1 ANSI V1 EN Figure 17 Communication module COM Breaker protection REQ650 ANSI 1MRK 505 269 BUS...

Page 37: ...I V1 EN Figure 18 Power supply module PSM 48 125V DC 1MRK006502 RB 5 PG 1 1 ANSI V1 EN Figure 19 Power supply module PSM 110 250V DC Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1 1...

Page 38: ...V1 EN Figure 20 Transformer module TRM 1MRK006502 RB 7 PG 1 1 ANSI V1 EN Figure 21 Binary input output BIO option Terminal X321 X324 Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1...

Page 39: ...nary input output BIO option Terminal X326 X329 Connection diagrams for REQ650 B11A 1MRK006502 SB 3 PG 1 1 ANSI V1 EN Figure 23 Communication module COM Breaker protection REQ650 ANSI 1MRK 505 269 BUS...

Page 40: ...I V1 EN Figure 24 Power supply module PSM 48 125V DC 1MRK006502 SB 5 PG 1 1 ANSI V1 EN Figure 25 Power supply module PSM 110 250V DC Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1 1...

Page 41: ...V1 EN Figure 26 Transformer module TRM 1MRK006502 SB 7 PG 1 1 ANSI V1 EN Figure 27 Binary input output BIO option Terminal X321 X324 Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1...

Page 42: ...1MRK006502 SB 8 PG 1 1 ANSI V1 EN Figure 28 Binary input output BIO option Terminal X326 X329 Breaker protection REQ650 ANSI 1MRK 505 269 BUS Product version 1 1 Issued April 2011 42 ABB...

Page 43: ...within which under specified conditions the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment under specified condit...

Page 44: ...1 s 100 A 500 A For 10 s 20 A 100 A Dynamic current withstand Half wave value 250 A 1250 A Input impedance 100 m 20 m Voltage inputs Rated voltage Vn 100 V AC 110 V AC 115 V AC 120 V AC Voltage withst...

Page 45: ...ge Max 15 of the DC value at frequency of 100 Hz Maximum interruption time in the auxiliary DC voltage without resetting the IED 50 ms at Vn Binary inputs and outputs Table 4 Binary inputs Description...

Page 46: ...ircuit time constant L R 40 ms at V 48 110 220 V DC 0 5 A 0 1 A 0 04 A Table 6 Power output relays without TCM function Description Value Rated voltage 250 V AC DC Continuous contact carry 8 A Make an...

Page 47: ...r rate LAN HMI port X0 1 CAT 6 S FTP or better 100 MBits s LAN1 X1 TCP IP protocol Fibre optic cable with LC connector 100 MBits s 1 Only available for the external HMI option Table 9 Fibre optic comm...

Page 48: ...IP40 Table 14 Environmental conditions Description Value Operating temperature range 25 55 C continuous Short time service temperature range 40 70 C 16h Note Degradation in MTBF and HMI performance ou...

Page 49: ...ANSI C37 90 2006 chapter 4 Dry heat tests operation storage 16 h at 70 C 96 h at 85 C IEC 60068 2 2 ANSI C37 90 2006 chapter 4 Damp heat tests steady state cyclic 240 h at 40 C humidity 93 6 cycles at...

Page 50: ...d common mode 10 V emf f 150 kHz 80 MHz IEC 61000 4 6 IEC 60255 22 6 level 3 Radiated amplitude modulated 20 V m rms f 80 1000 MHz and f 1 4 2 7 GHz IEC 61000 4 3 IEC 60255 22 3 level 3 ANSI C37 90 2...

Page 51: ...tions 0 50 ms No restart 0 s Correct behaviour at power down IEC 60255 11 IEC 61000 4 11 Electromagnetic emission tests EN 55011 class A IEC 60255 25 Conducted RF emission mains terminal 0 15 0 50 MHz...

Page 52: ...resistance measurements IEC 60255 5 ANSI C37 90 2005 Isolation resistance 100 M 500 V DC Protective bonding resistance IEC 60255 27 Resistance 0 1 60 s Table 18 Mechanical tests Description Reference...

Page 53: ...or value Accuracy Operate current 5 2500 of lBase 1 0 of In at I In 1 0 of I at I In Reset ratio 95 Operate time 20 ms typically at 0 to 2 x Iset Reset time 35 ms typically at 2 to 0 x Iset Critical...

Page 54: ...typically at 0 to 2 x Iset Reset time 35 ms typically at 2 to 0 x Iset Critical impulse time 10 ms typically at 0 to 2 x Iset Operate time 10 ms typically at 0 to 10 x Iset Reset time 45 ms typically...

Page 55: ...verse characteristics see table 69 table 70 and table 71 17 curve types See table 69 table 70 and table 71 Operate time nondirectional pickup function 20 ms typically at 0 to 2 x Iset Reset time picku...

Page 56: ...nverse characteristics see table 69 table 70 and table 71 17 curve types See table 69 table 70 and table 71 Operate time nondirectionalpickup function 20 ms typically at 0 to 2 x Iset Reset time picku...

Page 57: ...typically at 0 to 2 x Iset Reset time 30 ms typically at 2 to 0 x Iset Critical impulse time 10 ms typically at 0 to 2 x Iset Operate time 10 ms typically at 0 to 10 x Iset Reset time 40 ms typically...

Page 58: ...ve types See table 69 table 70 and table 71 Minimum polarizing voltage 1 100 of VBase 0 5 of Vn Minimum polarizing current 2 100 of IBase 1 0 of In Real part of source Z used for current polarization...

Page 59: ...0 5 mA 1 0 mA Operate level for non directional overcurrent 1 00 400 00 of lBase At low setting 10 50 mA 1 0 of In at I In 1 0 of I at I In 1 0 mA Operate level for non directional residual overvoltag...

Page 60: ...non directional residual overvoltage 70 ms typically at 0 8 to 1 5 x Uset Reset time non directional residual overvoltage 120 ms typically at 1 2 to 0 8 x Uset Operate time directional residual over...

Page 61: ...ION1356 V1 EN Equation 1 I actual measured current Ip load current before overload occurs Ib base current IBase Time constant t 0 1000 minutes IEC 60255 8 class 5 200 ms Alarm temperature 0 200 C 2 0...

Page 62: ...cally Reset time for current detection 10 ms maximum Table 30 Breaker failure protection CSPRBRF 50BF Function Range or value Accuracy Operate phase current 5 200 of lBase 1 0 of In at I In 1 0 of I a...

Page 63: ...value Accuracy Operate value current asymmetry level 0 100 1 0 of In Reset ratio 95 Time delay 0 000 60 000 s 0 5 25 ms Table 33 Broken conductor check BRCPTOC 46 Function Range or value Accuracy Mini...

Page 64: ...2 0 5000 0 of IBase 1 0 of Ir at I In 1 0 of I at I In Reset ratio 95 Low voltage level for memory 0 0 5 0 of VBase 0 5 of Vn Relay characteristic angle 180 180 degrees 2 0 degrees Relay operate angl...

Page 65: ...delay step 1 0 00 6000 00 s 0 5 25 ms Definite time delays step 2 0 000 60 000 s 0 5 25 ms Minimum operate time inverse characteristics 0 000 60 000 s 0 5 25 ms Operate time pickup function 30 ms typi...

Page 66: ...ime delay step 1 0 00 6000 00 s 0 5 25 ms Definite time delays step 2 0 000 60 000 s 0 5 25 ms Minimum operate time Inverse characteristics 0 000 60 000 s 0 5 25 ms Operate time pickup function 30 ms...

Page 67: ...2 0 000 60 000 s 0 5 25 ms Minimum operate time for step 1 inverse characteristic 0 000 60 000 s 0 5 25 ms Operate time pickup function 30 ms typically at 0 to 2 x Vset Reset time pickup function 40...

Page 68: ...50 ms typically at fset 0 5 Hz to fset 0 5 Hz Operate time delay 0 000 60 000 s 250 ms Restore time delay 0 000 60 000 s 150 ms Table 41 Overfrequency protection SAPTOF 81 Function Range or value Accu...

Page 69: ...In 5 0 of I at I In Table 44 Fuse failure supervision SDDRFUF Function Range or value Accuracy Operate voltage zero sequence 1 100 of VBase 1 0 of Vn Operate current zero sequence 1 100 of IBase 1 0 o...

Page 70: ...Vbus Vline 0 2 to 5 0 Frequency difference limit between bus and line 0 003 1 000 Hz 2 0 mHz Phase angle difference limit between bus and line 5 0 90 0 degrees 2 0 degrees Voltage difference limit bet...

Page 71: ...nc 0 00 6000 00 s Maximum trip pulse duration 0 000 60 000 s Inhibit reset time 0 000 60 000 s Reset time 0 00 6000 00 s Minimum time CB must be closed before AR becomes ready for autoreclosing cycle...

Page 72: ...ip pulse duration 0 000 60 000 s Inhibit reset time 0 000 60 000 s Reset time 0 00 6000 00 s Minimum time CB must be closed before AR becomes ready for autoreclosing cycle 0 00 6000 00 s CB check time...

Page 73: ...ity with cycle time Range or value Accuracy 5 ms 20 ms 100 ms AND 60 60 160 OR 60 60 160 XOR 10 10 20 INVERTER 30 30 80 SRMEMORY 10 10 20 RSMEMORY 10 10 20 GATE 10 10 20 PULSETIMER 10 10 20 0 000 9000...

Page 74: ...Sn 1 Apparent power S 0 1 x Vn V 1 5 x Vn 0 2 x In I 4 0 x In 1 0 of Sn at S Sn 1 0 of S at S Sn Apparent power S Three phase settings cos phi 1 0 5 of S at S Sn 0 5 of Sn at S Sn Power factor cos 0...

Page 75: ...aximum number of binary inputs 96 Maximum number of phasors in the Trip Value recorder per recording 30 Maximum number of indications in a disturbance report 96 Maximum number of events in the Event r...

Page 76: ...um number of recorded disturbances 100 Table 57 Event recorder DRPRDRE Function Value Buffer capacity Maximum number of events in disturbance report 150 Maximum number of disturbance reports 100 Resol...

Page 77: ...r value Accuracy Lower limit for the battery terminal voltage 60 140 of Vbat 1 0 of set battery voltage Reset ratio lower limit 105 Upper limit for the battery terminal voltage 60 140 of Vbat 1 0 of s...

Page 78: ...erations 0 9999 Setting of alarm for spring charging time 0 00 60 00 s 0 5 25 ms Time delay for gas pressure alarm 0 00 60 00 s 0 5 25 ms Time delay for gas pressure lockout 0 00 60 00 s 0 5 25 ms Met...

Page 79: ...HMI Description Value Front and side IP40 Dimensions Table 68 Dimensions Description Value Width 8 66 inches 220 mm Height 10 47 inches 265 9 mm 6U Depth 9 82 inches 249 5 mm Weight box 22 04 lbs 10 k...

Page 80: ...B 0 1217 P 2 0 ANSI IEEE C37 112 class 5 40 ms ANSI Very inverse A 19 61 B 0 491 P 2 0 ANSI Normal Inverse A 0 0086 B 0 0185 P 0 02 tr 0 46 ANSI Moderately Inverse A 0 0515 B 0 1140 P 0 02 ANSI Long...

Page 81: ...time inverse A 0 05 P 0 04 IEC Long time inverse A 120 P 1 0 Table 71 RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic 1 0 236 0 339 t td I E...

Page 82: ...1 unless otherwise stated Class 5 40 ms Type B curve 2 0 480 32 0 5 0 035 t td V VPickup VPickup EQUATION1662 V1 EN td 0 05 1 10 in steps of 0 01 unless otherwise stated Type C curve 3 0 480 32 0 5 0...

Page 83: ...EQUATION1658 V1 EN V Vmeasured td 0 05 1 10 in steps of 0 01 unless otherwise stated Class 5 40 ms Type B curve 2 0 480 0 055 32 0 5 td t VPickup V VPickup EQUATION1659 V1 EN V Vmeasured td 0 05 1 10...

Page 84: ...V Vmeasured td 0 05 1 10 in steps of 0 01 Class 5 40 ms Type B curve 2 0 480 32 0 5 0 035 t td V VPickup VPickup EQUATION1662 V1 EN td 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035 t t...

Page 85: ...Q650 Position SOFTWARE 1 Notes and Rules Version number Version no 1 1 Selection for position 1 1 1 Configuration alternatives 2 Notes and Rules Single breaker 3 phase 1 busbar ANSI A01A Single breake...

Page 86: ...g terminals R Power supply Slot position pPSM 100 240V AC 110 250V DC 9BO A 48 125V DC 9BO B Selection for position 7 Human machine interface 8 Notes and Rules Local human machine interface OL4000 ANS...

Page 87: ...nal for A01A p4 A p5 p6 optional for A11A B11A Selection for position 10 A Communication and processing module 11 Notes and Rules Slot position rear view pCOM 14BI IRIG B Ethernet LC ST B Selection fo...

Page 88: ...500 AA Rule Specify the number of printed manuals requested Operation manual ANSI Quantity 1MRK 500 093 UUS Technical manual ANSI Quantity 1MRK 505 267 UUS Commissioning manual ANSI Quantity 1MRK 505...

Page 89: ...505 268 UUS Product Guide 1MRK 505 269 BUS Type test certificate 1MRK 505 269 TUS 650 series manuals Identity number Communication protocol manual DNP3 1MRK 511 241 UUS Communication protocol manual...

Page 90: ...90...

Page 91: ...8 ABB Inc 3450 Harvester Road Burlington ON L7N 3W5 Canada Phone Toll Free 1 800 HELP 365 menu option 8 ABB Mexico S A de C V Paseo de las Americas No 31 Lomas Verdes 3a secc 53125 Naucalpan Estado De...

Reviews: