Table 42. Rate-of-change frequency protection SAPFRC (81)
Function
Range or value
Accuracy
Operate value, pickup function
(-10.00-10.00) Hz/s
± 10.0 mHz/s
Operate value, restore enable frequency (45.00 - 65.00) Hz
± 2.0 mHz
Timers
(0.000 - 60.000) s
<130 ms
Operate time, pickup function
At 50 Hz: 100 ms typically
At 60 Hz: 80 ms typically
-
Secondary system supervision
Table 43. Current circuit supervision CCSRDIF (87)
Function
Range or value
Accuracy
Operate current
(5-200)% of I
n
±
10.0% of I
n
at I
£
I
n
±
10.0% of I at I > I
n
Block current
(5-500)% of I
n
±
5.0% of I
n
at I
£
I
n
±
5.0% of I at I > I
n
Table 44. Fuse failure supervision SDDRFUF
Function
Range or value
Accuracy
Operate voltage, zero sequence
(1-100)% of VBase
± 1.0% of V
n
Operate current, zero sequence
(1–100)% of IBase
± 1.0% of I
n
Operate voltage, negative
sequence
(1–100)% of VBase
± 0.5% of V
n
Operate current, negative
sequence
(1–100)% of IBase
± 1.0% of I
n
Operate voltage change pickup
(1–100)% of VBase
± 5.0% of V
n
Operate current change pickup
(1–100)% of IBase
± 5.0% of I
n
Operate phase voltage
(1-100)% of VBase
± 0.5% of U
n
Operate phase current
(1-100)% of IBase
± 1.0% of I
n
Operate phase dead line voltage
(1-100)% of VBase
± 0.5% of U
n
Operate phase dead line current
(1-100)% of IBase
± 1.0% of I
n
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011