Table 54. Disturbance report DRPRDRE
Function
Range or value
Accuracy
Current recording
-
± 1,0% of I
r
at I ≤ I
r
± 1,0% of I at I > Ir
Voltage recording
-
± 1,0% of V
n
at V≤
V
n
± 1,0% of Vat V> V
n
Pre-fault time
(0.05–3.00) s
-
Post-fault time
(0.1–10.0) s
-
Limit time
(0.5–8.0) s
-
Maximum number of recordings
100, first in - first out
-
Time tagging resolution
1 ms
See time
synchronization
technical data
Maximum number of analog inputs
30 + 10 (ex
internally derived)
-
Maximum number of binary inputs
96
-
Maximum number of phasors in the Trip
Value recorder per recording
30
-
Maximum number of indications in a
disturbance report
96
-
Maximum number of events in the Event
recording per recording
150
-
Maximum number of events in the Sequential
of events
1000, first in - first out
-
Maximum total recording time (3.4 s
recording time and maximum number of
channels, typical value)
340 seconds (100
recordings) at 50 Hz, 280
seconds (80 recordings)
at 60 Hz
-
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
-
Recording bandwidth
(5-300) Hz
-
Breaker protection REQ650 ANSI
1MRK 505 269-BUS -
Product version: 1.1
Issued: April 2011
ABB
75