Section 15
Troubleshooting
15.1
Checking the self supervision signals
15.1.1
Checking the self supervision function
15.1.1.1
Determine the cause of an internal failure
This procedure describes how to navigate the menus in order to find the cause of an
internal failure when indicated by the flashing green LED on the HMI module.
Procedure
1.
Display the general diagnostics menu.
Navigate the menus to:
Diagnostics/IED status/General
2.
Scroll the supervision values to identify the reason for the failure.
Use the arrow buttons to scroll between values.
15.1.2
Self supervision HMI data
15.1.2.1
General IED status
The following table shows the general IED status signals.
Table 18:
Signals from the General menu in the diagnostics tree.
Indicated result
Possible reason
Proposed action
Internal fail Off
No problem detected.
None.
Internal fail On
A failure has occurred.
Check the rest of the indicated results to find
the fault.
Internal warning Off
No problem detected.
None.
Internal warning On
A warning has been
issued.
Check the rest of the indicated results to find
the fault.
Time synch Ready
No problem detected.
None.
Time synch Fail
No time synchronization.
Check the synchronization source for
problems.
If the problem persists, contact your ABB
representative for service.
Real time clock Ready
No problem detected.
None.
Real time clock Fail
The real time clock has
been reset.
Set the clock.
Table continues on next page
1MRK502053-UEN B
Section 15
Troubleshooting
Generator protection REG670 2.0 IEC
247
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...