EndSection1
M12541-186 v3
EndSection1
is set as a multiple of
IBase
. The default value 1.25 is generally
recommended. If the conditions are known more in detail, other values can be
chosen in order to increase or decrease the sensitivity.
EndSection2
M12541-189 v3
EndSection2
is set as a multiple of
IBase
. The default value 3.00 is generally
recommended. If the conditions are known more in detail, other values can be
chosen in order to increase or decrease the sensitivity.
SlopeSection2
M12541-192 v4
SlopeSection2
is set as a percentage value: [delta operate current/delta restrain
current] × 100%. The default value 40.0 is generally recommended. If the
conditions are known more in detail, other values can be chosen in order to
increase or decrease the sensitivity.
SlopeSection3
M12541-195 v4
SlopeSection3
is set as a percentage value: [delta operate current/delta restrain
current] × 100%. The default value 80.0 is generally recommended. If the
conditions are known more in detail, other values can be chosen in order to
increase or decrease the sensitivity.
6.1.3.3
The 2nd and 5th harmonic analysis
M12541-198 v5
The 2
nd
and 5
th
harmonic block scheme is permanently active only if an in-line
power transformer (A or B, alternatively both A and B) is part of the protected
circuit. This is a must due to phenomena specific for power transformers, such as
inrush and over-excitation. If there is no power transformer included in the
protected multi-terminal line circuit, then the 2
nd
and 5
th
harmonic block scheme is
only active under the following conditions:
•
If the bias current is lower than 1.25 times
IBase
.
•
Under external fault conditions.
•
If
NegSeqDiffEn
=
Off
(the default is
On
)
When the harmonic content is above the set level, the restrained differential
operation is blocked. However, if a fault has been classified as internal by the
negative sequence fault discriminator, any harmonic restraint is overridden.
I2/I1Ratio
M12541-201 v4
The set value is the ratio of the 2
nd
harmonic component of the differential current
to the fundamental frequency component of the differential current. To obtain this
information, the instantaneous differential current must be analyzed.
Transformer inrush currents cause high degrees of the 2
nd
harmonic in the
differential current. The default value of 15% is a reliable value to detect power
transformer inrush currents.
1MRK 505 393-UEN B
Section 6
Differential protection
Line differential protection RED650 2.2 IEC
91
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...