permissive (not strict) line protection scheme, for instance a power line carrier
(PLC) link, may not always be available. If lost, it can result in delayed tripping at
one end of a line. There is a possibility to extend the auto reclosing dead time in
such a case by use of the
PLCLOST
input, and the
tExtended t1
setting. Typical
setting in such a case:
Extended t1
=
On
and
tExtended t1
= 0.8 s.
t1 3PhHS
: There is also a separate time setting facility for three-phase high-speed
auto reclosing,
t1 3PhHS
. This high-speed auto reclosing is activated by the
STARTHS
input and is used when auto reclosing is done without the requirement of
synchrocheck conditions to be fulfilled. A typical dead time is 400ms.
t2 3Ph
,
t3 3Ph
,
t4 3Ph
,
t5 3Ph
: The delay of auto reclosing shot two and possible
later shots are usually set at 30s or more. A check that the circuit breaker duty
cycle can manage the selected setting must be done. The setting can in some cases
be restricted by national regulations. For multiple shots the setting of shots two to
five must be longer than the circuit breaker duty cycle time.
MasterSlave settings
Priority
: In single circuit breaker applications, one sets
Priority
= None. At
sequential reclosing the auto recloser for the first circuit breaker, e.g. near the
busbar, is set as master (High) and the auto recloser for the second circuit breaker
is set as slave (Low).
tWaitForMaster
: The slave should take the duration of the circuit breaker closing
time of the master into consideration before sending the circuit breaker closing
command. A setting
tWaitForMaster
sets a maximum wait time for the
WAIT
input
to reset. If the wait time expires, the auto reclosing cycle of the slave is inhibited.
The maximum wait time,
tWaitForMaster
for the second circuit breaker is set
longer than the auto reclosing dead time plus a margin for synchrocheck conditions
to be fulfilled for the first circuit breaker. Typical setting is 2sec.
tSlaveDeadTime
: When activating the
WAIT
input, in the auto recloser set as slave,
every dead timer is changed to the value of setting
tSlaveDeadTime
and holds back
the auto reclosing operation. When the
WAIT
input is reset at the time of a
successful reclosing of the first circuit breaker, the slave is released to continue the
auto reclosing sequence after the set
tSlaveDeadTime
. The reason for shortening
the time, for the normal dead timers with the value of
tSlaveDeadTime
, is to give
the slave permission to react almost immediately when the
WAIT
input resets. The
minimum settable time for
tSlaveDeadTime
is 0.1sec because both master and slave
should not send the circuit breaker closing command at the same time.
12.3
Apparatus control
IP14560-1 v3
12.3.1
Application
M13443-4 v14
The apparatus control is a functionality for control and supervising of circuit
breakers, disconnectors, and earthing switches within a bay. Permission to operate
1MRK 505 393-UEN B
Section 12
Control
Line differential protection RED650 2.2 IEC
251
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...