PPS in
IRIG-B
LDCM
diffSync
GPS
3xI
3xI
GPS
IED
Satellite-controlled clock
Merging unit (MU)
IED
IEC/UCA 61850-
9-2LE
IEC17000070-1-en.vsd
IRIG-B
Satellite-controlled clock
GPS
TRM
IEC17000070 V1 EN-US
Figure 174:
Time synchronization of merging unit and IED
The parameter
DiffSync
for the LDCM needs to be set to
GPS
and the
GPSSyncErr
needs to be set to
Block
.
In "ECHO" mode MU and IED still need to be synchronized. In this case they can
be synchronized with either PPS or IRIG-B.
Section 21
1MRK 505 393-UEN B
Basic IED functions
422
Line differential protection RED650 2.2 IEC
Application manual