Figure 150:
Example of a station configuration with separated process bus and
station bus
The IED can get analog values simultaneously from a classical CT or VT and from
a Merging Unit, like in this example:
The merging units (MU) are called so because they can gather analog values from
one or more measuring transformers, sample the data and send the data over
process bus to other clients (or subscribers) in the system. Some merging units are
able to get data from classical measuring transformers, others from non-
conventional measuring transducers and yet others can pick up data from both
types. The electronic part of a non-conventional measuring transducer (like a
Rogowski coil or a capacitive divider) can represent a MU by itself as long as it
can send sampled data over process bus.
Section 18
1MRK 505 393-UEN B
Station communication
366
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...