phase equality. At the setting of 10 mHz, the beat time is 100 seconds and the
setting would thus need to be at least
tMinSynch
plus 100 seconds. If the network
frequencies are expected to be outside the limits from the start, a margin needs to
be added. A typical setting is 600 seconds.
tMinSynch
The setting
tMinSynch
is set to limit the minimum time at which the synchronizing
closing attempt is given. The synchronizing function will not give a closing
command within this time, from when the synchronizing is started, even if a
synchronizing condition is fulfilled. A typical setting is 200 ms.
Synchrocheck settings
OperationSC
The
OperationSC
setting
Off
disables the synchrocheck function and sets the
outputs AUTOSYOK, MANSYOK, TSTAUTSY and TSTMANSY to low. With
the setting
On
, the function is in the service mode and the output signal depends on
the input conditions.
UHighBusSC
and
UHighLineSC
The voltage level settings must be chosen in relation to the bus or line network
voltage. The threshold voltages
UHighBusSC
and
UHighLineSC
have to be set
lower than the value at which the breaker is expected to close with the synchronism
check. A typical value can be 80% of the base voltages.
UDiffSC
The setting for voltage difference between line and bus in p.u. This setting in p.u. is
defined as (U-Bus/
GblBaseSelBus
) - (U-Line/
GblBaseSelLine
). A normal setting is
0,10-0,15 p.u.
FreqDiffM
and
FreqDiffA
The frequency difference level settings,
FreqDiffM
and
FreqDiffA
, shall be chosen
depending on the condition in the network. At steady conditions a low frequency
difference setting is needed, where the
FreqDiffM
setting is used. For autoreclosing
a bigger frequency difference setting is preferable, where the
FreqDiffA
setting is
used. A typical value for
FreqDiffM
can be10 mHz, and a typical value for
FreqDiffA
can be 100-200 mHz.
PhaseDiffM
and
PhaseDiffA
The phase angle difference level settings,
PhaseDiffM
and
PhaseDiffA
, shall also
be chosen depending on conditions in the network. The phase angle setting must be
chosen to allow closing under maximum load condition. A typical maximum value
in heavy-loaded networks can be 45 degrees, whereas in most networks the
maximum occurring angle is below 25 degrees. The
PhaseDiffM
setting is a
limitation to
PhaseDiffA
setting. Fluctuations occurring at high speed autoreclosing
limit
PhaseDiffA
setting.
1MRK 505 393-UEN B
Section 12
Control
Line differential protection RED650 2.2 IEC
227
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...