4.2.3
Relationships between setting parameter Base Current, CT
rated primary current and minimum pickup of a protection
IED
GUID-8EB19363-9178-4F04-A6AC-AF0C2F99C5AB v1
Note that for all line protection applications (e.g. distance protection or line
differential protection) the parameter Base Current (i.e. IBase setting in the IED)
used by the relevant protection function, shall always be set equal to the largest
rated CT primary current among all CTs involved in the protection scheme. The
rated CT primary current value is set as parameter
CTPrim
under the IED TRM
settings.
For all other protection applications (e.g. generator, shunt reactor, shunt capacitor
and transformer protection) it is typically desirable to set
IBase
parameter equal to
the rated current of the protected object. However this is only recommended to do
if the rated current of the protected object is within the range of 40% to 120% of
the selected CT rated primary current. If for any reason (e.g. high maximum short
circuit current) the rated current of the protected object is less than 40% of the
rated CT primary current, it is strongly recommended to set the parameter
IBase
in
the IED to be equal to the largest rated CT primary current among all CTs involved
in the protection scheme and installed on the same voltage level. This will
effectively make the protection scheme less sensitive; however, such measures are
necessary in order to avoid possible problems with loss of the measurement
accuracy in the IED.
Regardless of the applied relationship between the
IBase
parameter and the rated
CT primary current, the corresponding minimum pickup of the function on the CT
secondary side must always be verified. It is strongly recommended that the
minimum pickup of any instantaneous protection function (e.g. differential,
restricted earth fault, distance, instantaneous overcurrent, etc.) shall under no
circumstances be less than 4% of the used IED CT input rating (i.e. 1A or 5A).
This corresponds to 40mA secondary for IED 1A rated inputs and to 200mA
secondary for IED 5A rated inputs used by the function. This shall be individually
verified for all current inputs involved in the protection scheme.
Note that exceptions from the above 4% rule may be acceptable for very special
applications (e.g. when Multipurpose filter SMAIHPAC is involved in the
protection scheme).
4.2.4
Setting of voltage channels
SEMOD55055-44 v4
As the IED uses primary system quantities, the main VT ratios must be known to
the IED. This is done by setting the two parameters
VTsec
and
VTprim
for each
voltage channel. The phase-to-phase value can be used even if each channel is
connected to a phase-to-earth voltage from the VT.
4.2.4.1
Example
SEMOD55055-47 v3
Consider a VT with the following data:
1MRK 505 393-UEN B
Section 4
Analog inputs
Line differential protection RED650 2.2 IEC
55
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...