The positive sequence line charging current is calculated according to equation
.
arg
1
1
1
2
3
3
Ch
e
U
U
I
XC
f C
p
=
×
×
=
×
EQUATION1417 V2 EN-US
(Equation 12)
where:
U
is system voltage
X
C1
is capacitive positive sequence reactance of the line
f
is system frequency
C
1
is positive sequence line capacitance
If the charging current compensation is enabled, the setting of
IdMin
must be:
IdMin
≥ 1.2 × ICharge, concidering some margin in the setting. If the charging
current compensation is disabled, the setting of
IdMin
must be
IdMin
≥ 2.5 ×
ICharge. In many cases, the charging current is quite small, which makes the lower
limit of the setting range, that is 20% of
IBase
the practical limit of sensitivity.
When a power transformer is included in the protected zone, the setting of
IdMin
shall be the highest of recommendations considering charging current as described
above and 0.3 ×
IBase
.
IdMinHigh
M12541-165 v5
The
IdMinHigh
setting is a multiple of
IBase
and used to temporarily decrease
sensitivity in situations when the line is energized.
Energizing a line can cause transient charging currents to appear. These currents
are pure differential currents, but as they are rich in harmonics, they can partly be
measured by the differential protection, which in this case measures the Fourier-
filtered differential current. Desensitizing the differential protection in this situation
by using
IdMinHigh
instead of
IdMin
is a safety precaution, and a setting of 1.00 ×
IBase
should be suitable in most cases.
If there is a power transformer included in the protected zone, energizing the line
means that the transformer is energized at the same time. If the transformer
nominal current is more than 50% of
IBase
,
IdMinHigh
is recommended to be set
at 2.00 ×
IBase
, otherwise it can be kept at 1.00 ×
IBase
.
Switching of a transformer inside the protected zone does not normally occur. If the
transformer is equipped with a breaker on the HV side, it would most probably not
be included in the protected zone. However, tap transformers are sometimes
connected with a disconnector on the HV side, and the normal procedure is then to
energize the transformer with the disconnector. In such cases, where the tap (shunt)
power transformer's power rating is relatively small in comparison to the normal
load of the circuit, connecting the tap power transformer to the voltage source, that
1MRK 505 393-UEN B
Section 6
Differential protection
Line differential protection RED650 2.2 IEC
89
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...