DFTReference
: Reference DFT for the SMAI block use.
These DFT reference block settings decide DFT reference for DFT calculations.
The setting
InternalDFTRef
will use fixed DFT reference based on set system
frequency.
DFTRefGrp(n)
will use DFT reference from the selected group block,
when own group is selected, an adaptive DFT reference will be used based on
calculated signal frequency from own group. The setting
ExternalDFTRef
will use
reference based on what is connected to input DFTSPFC.
The setting
ConnectionType
: Connection type for that specific instance (n) of the
SMAI (if it is
Ph-N
or
Ph-Ph
). Depending on connection type setting the not
connected
Ph-N
or
Ph-Ph
outputs will be calculated as long as they are possible to
calculate. E.g. at
Ph-Ph
connection L1, L2 and L3 will be calculated for use in
symmetrical situations. If N component should be used respectively the phase
component during faults I
N
/U
N
must be connected to input 4.
Negation
: If the user wants to negate the 3ph signal, it is possible to choose to
negate only the phase signals
Negate3Ph
, only the neutral signal
NegateN
or both
NeN
. negation means rotation with 180° of the vectors.
GlobalBaseSel
: Selects the global base value group used by the function to define
(
IBase
), (
UBase
) and (
SBase
).
MinValFreqMeas
: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of UBase (for each instance n).
Settings
DFTRefExtOut
and
DFTReference
shall be set to default
value
InternalDFTRef
if no VT inputs are available.
Even if the user sets the
AnalogInputType
of a SMAI block to
“
Current
”, the
MinValFreqMeas
is still visible. However, using the
current channel values as base for frequency measurement is
not
recommendable
for a number of reasons, not last among them
being the low level of currents that one can have in normal
operating conditions.
Examples of adaptive frequency tracking
Preprocessing block shall only be used to feed functions within the
same execution cycles (e.g. use preprocessing block with cycle 1 to
feed transformer differential protection). The only exceptions are
measurement functions (CVMMXN, CMMXU,VMMXU, etc.)
which shall be fed by preprocessing blocks with cycle 8.
When two or more preprocessing blocks are used to feed one
protection function (e.g. over-power function GOPPDOP), it is of
1MRK 505 393-UEN B
Section 21
Basic IED functions
Line differential protection RED650 2.2 IEC
411
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...