DC Input data and solar array requirements
Inverter type PVS300-TL- 3300W-2 4000W-2 4600W-2 6000W-2 8000W-2
Nominal solar array power
3400 W
4200 W
4800 W
6200 W
8300 W
Maximum solar array power
3700 W
4500 W
5200 W
6700 W
8900 W
Operational voltage range, MPPT
335 V to 800 V
Maximum solar array open circuit
voltage
900 V
Nominal operational voltage
480 V
Starting voltage level for grid feeding
370 V when actual grid voltage is at nominal level. The
starting voltage level increases and decreases as the
grid voltage varies.
Wake up voltage
250 V
Maximum solar array short circuit
current
10.5 A
12.7 A
14.6 A
19.0 A
25.4 A
Maximum inverter back feed current to
the array
25.4 A (back feed current limited by the string fuses)
Number of MPP trackers
1
Number of parallel input connections
4
Connector type
Quick connector 30A, Multicontact MC4,
types PV-KBT4/6 (DC+) and PV-KST4/6 (DC-)
Reverse polarity protection type
Short circuit diode, monitored
Insulation monitoring
Impedance measurement between DC terminals and
ground
Surge protection
SPD between all DC terminals and ground, monitored
Summary of Contents for PVS300
Page 1: ...ABB solar inverters Product manual PVS300 string inverters ...
Page 4: ......
Page 9: ...Table of contents 9 Further information ...
Page 10: ...10 Table of contents ...
Page 34: ...34 Operation basics and hardware description ...
Page 48: ...48 Planning the installation ...
Page 76: ...76 Installation checklist ...
Page 110: ...110 Troubleshooting ...
Page 120: ...120 Technical data ...
Page 122: ...122 Dimension drawing 3AUA0000094904 ...
Page 123: ...Dimension drawing 123 Required clearances for cooling ...
Page 124: ...124 Dimension drawing ...
Page 126: ...126 Navigation map The navigation map ...
Page 127: ...Navigation map 127 ...
Page 128: ...128 Navigation map ...
Page 130: ...3AUA0000096321 Rev B EN EFFECTIVE 2013 03 14 Contact us www abb com solar ...