04-3788_ABB_OPM_PVA11 6-10kVA-RT_EN_140423
Page 28/37 ABB
Modifications reserved
Submenu item
Description
Optional Values
Default value
ECO mode (HE)
voltage low limit
When the voltage in the bypass is below this limit, the
UPS changes running mode.
5%~10%
5%
ECO mode (HE)
voltage high limit
When the voltage in the bypass is above this limit, the
UPS changes running mode.
5%~10%
5%
ECO mode (HE)
frequency low limit
When the frequency in the bypass is below this limit,
the UPS changes running mode.
1%~10%
5%
ECO mode (HE)
frequency high limit
When the frequency in the bypass is above this limit,
the UPS changes running mode.
1%~10%
5%
External Battery
module***
Define the number of battery modules. If number is
higher than 4, it should be configured through the
monitoring software
0-4
0
Set running time
Set the UPS running time mainly used for test
purposes
Day:hour:minute:second
0000:0000:00~9999
23:59:59
Running time
LCD contrast
Changes the light contrast in the LCD panel
-5~+5
0
Table 1: Settings menu information
**Read Section 3.2, before using ECO-mode (HE mode) or converter function.
***Ensure the real battery quantity is same as the settings not to damage the batteries.
Figure 37: Setting menu tree