2.2.2 Positioning
PowerValue 11 RT can be mounted in a rack or in a standalone configuration. Follow the instructions in this
section accordingly to the installation requirements.
Note that water condensing may occur if the UPS is unpacked in a very low temperature environment. In this
case it is necessary to wait until the UPS is fully dried inside out before proceeding installation and use to
avoid hazards and electric shock.
2.2.2.1 Rack Mount Installation
1. Identify the rail holes in the rack for positioning the cabinet. Position the rails in the bottom of the 3U
space for 6kVA units and 5U space for 10kVA units.
2. Slide the cabinet into the rack as indicated in Figure 2.
Figure 2: Rack mount installation
If installing additional UPS, repeat procedures 1 and 2 for each cabinet.
Connecting the External Battery Modules
PowerValue 11 RT 6kVA
WARNING!
THIS TYPE OF CONNECTION MUST BE CARRIED OUT BY QUALIFIED
ELECTRICAL PERSONNEL.
CONNECT AN APPROPRIATE BREAKER BETWEEN UPS AND BATTERIES.
1. Remove the front panel of the UPS and of the external battery modules.
2. Plug the External Battery Enclosure cable into the UPS battery connector as indicated in
3. Figure
3
.
Figure 3: Battery Module Connections
4. Position and screw the UPS and the Battery Module front panel.