3.4.2.4 Identification
Press
on the Identification menu to navigate through its data. The identification information includes UPS
serial number, firmware serial number and-model type.
Press >1s to return to the last main menu.
Figure 36: Identification menu tree
3.4.2.5 User’s Settings
Contact your local distributor for further information before using the settings. Some settings can impact on
the performance of the UPS and others can enable and disable functions within the UPS. Failures and
reduced protection can occur if the equipment is not set in an adequate way. Note that most settings should
be done only with the UPS in
bypass-mode
.
If the password is enabled, the user must enter the password
USER
by pressing the buttons , and
. It
is used mainly to protect against modifications in the Settings menu. The possible operations are indicated in
Table 1.
Submenu item
Description
Optional Values
Default value
Language
Select menu language
Chinese/English
English
User password*
Protects against settings modifications
enabled/disabled
disabled
Audio alarm
Enable/disable alarm sounds
enabled/disabled
enabled
Output voltage
Define local rated output voltage
208/220/230/240V
230V
Output frequency
Define local rated output frequency
autosensing/50/60Hz
autosensing
Power strategy**
or Running mode
Define the UPS running mode to normal, ECO-mode
(or HE high efficiency) and converter mode
normal/high efficiency/
converter
normal
DC start
Start the UPS from the batteries (without mains
power)
enabled/disabled
enabled
Site wiring fault alarm
Phase and neutral cables are connected in reversed
positions.
enabled/disabled
enabled
Ambient temperature
warning
Temperature is over the limit supported by the UPS
enabled/disabled
enabled
Automatic battery tests
period
Define the frequency of the battery tests
0-31 days
7days
Auto restart
After power outage, the loads restart automatically
when mains power is recovered.
enabled/disabled
enabled
Automatic overload
restart
The UPS is automatically restarted if it shut downs for
overload.
enabled/disabled
enabled
Auto bypass
The automatic bypass can be disabled for countries
where the power supply is very unstable. UPS runs
only online or on battery.
enabled/disabled
enabled
Short circuit clearance
- When enabled, short circuit will last for 4s before
cutting off the output. If short circuit is removed during
this time, the UPS will continue to run normally.
- When disabled, short circuit will only last for 100ms
before UPS output is cut off.
enabled/disabled
disabled
Redundancy lost (in
parallel UPS systems)
One of the parallel units have been disconnected from
the system
enable/disabled
enabled
Bypass voltage low
limit
When the voltage in the bypass is below this limit, the
UPS changes running mode.
120~215V
184V
Bypass voltage high
limit
When the voltage in the bypass is above this limit, the
UPS changes running mode.
245~276V
264V
Bypass frequency low
limit
When the frequency in the bypass is below this limit,
the UPS changes running mode.
1%~10%
10%
Bypass frequency high
limit
When the frequency in the bypass is above this limit,
the UPS changes running mode.
1%~10%
10%