04-3788_ABB_OPM_PVA11 6-10kVA-RT_EN_140423
Page 25/37 ABB
Modifications reserved
3.4.2 Navigation
To navigate through the UPS screens, the scroll buttons are used. From the main screen, press or for
information on alarm, parallel system and battery.
From the main screen, press
for more than 1s to enter the main menu. The main menu includes the
following submenus: UPS status, event log, measurements, control, identification, settings. Figure 33 shows
details on how to navigate through the menus and submenus.
Figure 33: Main menu tree
3.4.2.1 Event log
To enter this menu, press
. In this menu, the last 50 events, alarms and faults occurred in the UPS are
displayed. The alarms are indicated by the corresponding illustration, event code and operating time of UPS
when the event occurred. To navigate through the events and alarms, press
or .
3.4.2.2 Measurements
To enter this menu, press
. Several measurements are displayed in the menu such as output voltage,
frequency, current, load capacity, input voltage and frequency. To navigate through the measurements, press
or . To return to the last menu (event log), press for more than 1s.
3.4.2.3 Control
From this menu, the user can control some features of the UPS. To modify the parameters, press
. Then
scroll up or down to modify the parameters. To confirm the selection, press
for more than 1s. The possible
operations are indicated below:
Control
Description
Possible Values
Default
Values
Buzzer mute
Mute the UPS sound
No/Yes
No
Single UPS turn off
Turn off one UPS in a parallel system
No/Yes
No
Single UPS battery
test
Initiate test of the batteries of a single UPS
Battery test running /
passed / failed /
interrupted / aborted
Battery not
tested
Parallel UPS battery
test
Initiate test of the batteries of a group of UPSs
Clear EPO status
Remove UPS from emergency power off status
No/Yes
No
Reset fault state
Reset warning, alarming status and buzzer
No/Yes
No
Clear event log
Reset all the events from the log file
No/Yes
No
Restore factory
settings
Recover all settings in the LCD menu and the
EPO polarity and locks the DC start-up (can be
executed only when UPS is in bypass mode)
No/Yes
No