![ABB NETA-21 User Manual Download Page 30](http://html.mh-extra.com/html/abb/neta-21/neta-21_user-manual_3353030.webp)
30 Electrical installation
Connection via the EIA-485 port with a Modbus/RTU adapter
module
A maximum of 32 monitored Modbus/RTU devices can be connected to the same EIA-485
network. The following figure is an example of an allowable topology:
The X3 EIA-485 connector for a Modbus network is located at the bottom of the NETA-21.
See the bottom layout in section
Layout of the NETA-21 and the NEXA-21
. The EIA-485
(RS-485) cabling requires a shielded dual twisted pair cable. The nominal impedance of
the cable must between 100…150 ohm.
Connecting the NETA-21 to the RS-485 network
Connect the bus cable to connector X3 on the NETA-21.
The pin allocation of the X3 connector is shown below.
Signals DATA_A, DATA_B and GND_B must always be connected to all communication
modules and to the NETA-21.
X1
Description
1
SHLD
Bus cable shield. Connected internally to a ground clip via an RC filter. Depending on
the installation environment, the shielding is connected to this pin on the NETA-21 or
on another location on the EIA-485 network.
2
DATA_B Data positive
3
DATA_A Data negative
4
GND_B
Isolated signal ground
NETA-21
ABB drive with
an FSCA-01
or with an
embedded
EIA-485 port
Other slave
device
T = Termination
T
ABB drive with
an FSCA-01
or with an
embedded
EIA-485 port
ABB drive with
an FSCA-01
or with an
embedded
EIA-485 port
Other slave
device
Other slave
device
T
ABB drive with
an FSCA-01
or with an
embedded
EIA-485 port
1
2
3
4
Summary of Contents for NETA-21
Page 2: ......
Page 4: ......
Page 18: ...18 Introduction to the manual ...
Page 32: ...32 Electrical installation ...
Page 42: ...42 Start up ...
Page 50: ...50 Program features ...
Page 56: ...56 Front page ...
Page 68: ...68 Users ...
Page 114: ...114 Networks ...
Page 150: ...150 Reporting ...
Page 172: ...172 Security ...
Page 176: ...176 Memory card ...
Page 184: ...184 Frequently asked questions ...
Page 190: ...190 Diagnostics and troubleshooting ...
Page 194: ...194 Technical data ...