I.L. 40-385.5
7-6
(3)
Fault Data Display
The MDAR (REL-300) saves the latest 16 fault records, but only the latest two fault records can be
accessed from the front panel. For complete 16 fault records, one of the communication interface
devices are required.
Each set of fault target record display shows the following information:
Display
Information
Function
Value
Field
Field
Fault occurred at:
1.date
DATE
XX.XX (month.day)
2.year
YEAR
XXXX
3.time
TIME
XX.XX (hour.minute)
4.second
SEC
XX.XX (second)
Fault type
FTYP
AG/BG/CG/AB/BC/CA
ABG/BCG/CAG/ABC
BKR. #1 DA tripped
BK1A
YES/NO
BKR. #1 DB tripped
BK1B
“
BKR. #1 DC tripped
BK1C
“
BKR. #2 DA tripped
BK2A
YES/NO
BKR. #2 DB tripped
BK2B “
BKR. #2 DC tripped
BK2C
“
Zone-1 phase tripped
Z1P
YES/NO
Zone-1 ground tripped
Z1G
“
Zone-2 phase tripped
Z2P
“
Zone-2 ground tripped
Z2G
“
Zone-3 phase tripped
Z3P
YES/NO
Zone-3 ground tripped
Z3G
“
Pilot phase tripped
PLTP
“
Pilot ground tripped
PLTG
“
High set phase tripped
ITP
“
High set ground tripped
ITG
“
Close-into fault trip
CIF
“
Load-loss tripped
LLT
“
Ground backup tripped
GB
“
*Sec. fault tripped(SPF)
SPF
“
*62T tripped
62T
“
*
Optional functions for single-pole trip.