I.L. 40-385.5
A-23
TABLE A-4. RECOMMENDED JUMPER POSITIONS (V2.6X)
OUTER CHASSIS
An External jumper between FT-Switch 13 and 14 of 2FT-14 should be connected permanently.
(Refer to terminals 2 & 4 of 2 FT-14 on Figure 5.)
INTERCONNECT Module
JMP 1 to 6, & 13
For the rated input dc voltage
JMP 7 & 9
For Single Pole Trip Application (XTRIPB)
JMP 8 & 10
For the trip alarm (AL2-2)
JMP 11 & 12
For MDAR with FT switches only
MICROPROCESSOR Module
JUMPER
POSITION
FUNCTION
JMP 1
1-2
EEPROM (8kx8)
JMP 2
2-3
Single-pole trip option
JMP 2
1-2
Three pole trip
JMP 3
OUT
Standard for Rotation ABC
JMP 4
OUT
No dropout time delay for trip contacts
JMP 5
OUT
Disable output contact test
JMP 6
OUT
Normal operation
JMP 8 & 9
1-2
RAM (32kx8)
JMP 10, 11 & 12
IN/OUT
Spare jumpers
POWER SUPPLY Module
JMP1
1-2
Carrier Stop
NO
2-3
Carrier Stop
NC
JMP2
1-2
Carrier Send
NO
2-3
Carrier Send
NC