Step
Action for Voltage Calibration
1.
Using the Meter Calibration Menus, reset the plant voltage reading by selecting RESET VOLTAGE. Press
the Enter key to reset the voltage.
This will remove any pre
-
existing user calibrated values if they exist.
2.
Wait at least 5 seconds and press the ESCAPE key.
3.
Select CALIBRATE VOLTAGE. Use the Arrows, and UP/DOWN keys to
calibrate the system voltage. Press ENTER to save.
NOTE:
The controller will not allow changes greater than +/
-
0.5V of the
displayed voltage.
4.
Press the <ESCAPE> key until the default screen is displayed. Verify
that the plant voltage reading now agrees with the calibrated DVM.
NOTE:
The DVM reading will be the one to change since Rectifier Manager will adjust rectifier outputs as
necessary per the calibration performed.
Step
Action for Current Calibration
NOTE:
The following procedure is applicable only in plants with Load shunts
Summary of Contents for GPS4827
Page 12: ...Page 12 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 20: ...Page 20 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 24: ...Page 24 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 30: ...Page 30 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 34: ...Page 34 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 62: ...Page 62 Copyright 2021 ABB All rights reserved Control and Operations Menu Map ...
Page 63: ...Page 63 Copyright 2021 ABB All rights reserved Status Menu Map ...
Page 64: ...Page 64 Copyright 2021 ABB All rights reserved History Menu Map Statistics Menu Map ...
Page 80: ...Page 80 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 90: ...Page 90 Copyright 2021 ABB All rights reserved This page intentionally left blank ...