ALARM THRESHOLDS
High Voltage
When the plant voltage exceeds this threshold, the plant High
Voltage Alarm (HVA) is turned ON, and the controller will send a
signal to the rectifiers to shut down in an orderly and timely
fashion. This will also light the Major (MJ) LED, and activate the
PMJ relay (assuming there is no alarm with CRITICAL severity
level active). Move the cursor to the fields and use the <+> or
<
-
> key to adjust the High Voltage shut down alarm for FLOAT
mode to the desired level. Press <ENTER> to save the change.
High Voltage Float
When the plant voltage exceeds this threshold, the plant High
Float Voltage Alarm (HFV) is turned ON, and this will also light
the Minor LED, activate the PMN contact closure (assuming
there is no alarm with CRITICAL or MAJOR severity level active).
The purpose of this alarm is to indicate that the plant voltage is
high probably due to an adjustment in the plant rather than due
to a failure. This alarm allows the High Voltage (HV) shutdown
threshold to be raised slightly, thus reducing the number of
nuisance shutdowns without decreasing the plant reliability.
Move the cursor to the fields and use the <+> or <
-
> key to
adjust the High Voltage shut down alarm for FLOAT mode to the
desired level (normally less than the HV threshold). Press
<ENTER> to save the change.
Battery on
Discharge
If the plant voltage is less than the threshold value, the Battery
Discharge alarm is turned ON, this in turn activates the PMJ and
BD relay, light the MAJ and BD LEDs. Move the cursor to the
fields, and use the <+> or <
-
> key to adjust the threshold to the
desired level. Press <ENTER> to save the change.
Very Low Voltage
This alarm threshold is used to indicate that the system voltage
is very low, and that the batteries have discharged to a
dangerously low depth. When the plant voltage falls below this
level, the Very Low Voltage (VLV) and Power Critical alarm will be
generated. Move the cursor to the field and use the <+> or
<
-
> key to adjust the threshold value. Press
<ENTER> to save the change.
Summary of Contents for GPS4827
Page 12: ...Page 12 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 20: ...Page 20 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 24: ...Page 24 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 30: ...Page 30 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 34: ...Page 34 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 62: ...Page 62 Copyright 2021 ABB All rights reserved Control and Operations Menu Map ...
Page 63: ...Page 63 Copyright 2021 ABB All rights reserved Status Menu Map ...
Page 64: ...Page 64 Copyright 2021 ABB All rights reserved History Menu Map Statistics Menu Map ...
Page 80: ...Page 80 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 90: ...Page 90 Copyright 2021 ABB All rights reserved This page intentionally left blank ...