34
ABB i-bus
®
EIB / KNX
32 Input – Window contact (EIS 1: 1 Bit)
The Fan Coil Controller sends the status of the local window contact or the
binary input via the EIB / KNX using this communication object.
Telegram value:
“0”:
Contact open (input normal)
“1”:
Contact closed (input normal)
“0”:
Contact closed (input inverted)
“1”:
Contact open (input inverted)
33 Switch output – Switch output 1 (EIS 1: 1 Bit)
34 Switch output – Switch output 2 (EIS 1: 1 Bit)
35 Switch output – Switch output 3 (EIS 1: 1 Bit)
These communication objects are used if no fan is connected but any other
electrical loads are connected to the switch outputs of the Fan Coil Controller.
If the option “local (max. 3 speeds)” is set for the parameter
Type of fan
,
incoming telegrams at this communication object are not executed.
The floating outputs of the Fan Coil Controller are switched on or off via
these communication objects, for example to control the lighting or an
electric heating system.
Telegram value:
“0”:
Output off (contact open)
“1”:
Output on (contact closed)
The default values are printed in italics. Additional parameters can be
displayed or hidden via the button “Low Access/High Access”.
In the following section, all the parameters are described which are available
when “High Access” is selected.
Fig. 22: Parameter window: “General”
Project design and programming
4.2
Description of the
parameters
4.2.1 Parameter
window:
“General”