37
ABB i-bus
®
EIB / KNX
Sending of error signal
Options: –
no
repetition
–
cyclical repetition
For setting the send repetition in the event of an error message. If the option
“no repetition” is selected, the error signal is only sent if there is a change
in the object value. If the option “cyclical repetition” is set, the object value
is sent according to the parameterised
Period for cyclical sending
for the
Sending of the actual temperature
.
Sending of the actual temperature
Cyclical sending
Options: –
on
–
off
Activation of the cyclical transmission function for the actual temperature.
This parameter is only visible if the option “local” is set for the parameter
Sensor for measuring the actual temperature
.
Period for cyclical sending
Options [min.]: – 2...255
(2)
Setting the cyclical transmission period for the actual temperature.
This parameter is only visible if the option “on” is selected for the parameter
Cyclical sending
.
Differential value for sending
Options [°C]: – 0.1...1.0
(0.5)
Setting the temperature change at which the actual temperature is sent in
addition to being sent after a change in value. This parameter is only visible
if the option “local” has been set for the parameter
Sensor for measuring
the actual temperature
.
Fig. 24: Parameter window: “External temperature”
4.2.3 Parameter
window:
“External
temperature”
Project design and programming