Fig. 23: Parameter window: “Actual temperature”
Sensor for measuring the actual temperature
Options: –
local
–
via
EIB
Setting the temperature sensor. If the temperature sensor TS/K 1.1 is con-
nected to the Fan Coil Controller, the option “local” must be selected. In this
case, the three parameters for
Sending of the actual temperature
become
visible. If the temperature is received via the EIB / KNX, the option “via EIB”
must be set.
Correction value
Options [°C]: – -3,0...3,0
(0,0)
Correction of the value measured by the temperature sensor TS/K 1.1 or the
actual value received via the EIB / KNX.
Monitoring period of actual temperature
Options [min.]: – 2...255
(10)
Setting the monitoring period for the actual temperature (local and via the
EIB / KNX).
If a sensor value is received via the EIB / KNX, the monitoring period should
be selected so that it is at least twice as long as the cyclical transmission
period of the sensor so that an error message is not sent immediately when
a signal fails to appear.
If the actual temperature is not received, the Fan Coil Controller regulates
the heating valve according to the parameterised
Control value (heating)
when actual temperature is absent or in event of frost
(parameter window
“Temperature monitoring”).