ABB | E-Hub 2.0
48 | © 2019 ABB | DOC. N° 1SDH002109A1001 - ECN000125349 - Rev. A
Basic configuration via Ekip Connect 3 | Communication Settings
Language
The E-Hub 2.0 only supports the
English
currently.
3 - Communication Settings
Connectivity Settings
This page will set the connectivity parameters.
• Click
Connectivity > To the devices
Fig. 28
Serial Port Parameters
Parameters
Description
Default
Baud rate
RS-485 Port baud rate: 9600 bit/s
19200 bit/s
38400 bit/s
19200 bit/s
Protocol
E81: Even parity, 8 data bits, 1 stop bit
O81: Odd parity, 8 data bits, 1 stop bit
N82: None parity, 8 data bits, 2 stop bit
N81: None parity, 8 data bits, 1 stop bit
E81
• Click
Save
the configuration.
• Reboot the E-Hub 2.0 will make the configuration valid.