132
CoriolisMaster FCB400, FCH400
CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E
… 10 Diagnosis / error messages
Overview
The counter readings and the states of the current outputs and the alarm output are represented by symbols; please see the table
below.
Symbol Description
Counter
stop
—
No change, current value
1)
When the error occurs, the corresponding measurement variable is calculated with the temperature 20 °C.
2)
When the error occurs, the corresponding measurement variable is set to the value with density = 1.
HOLD
The last ‘good’ measured value is retained.
Alarm
(general)
High
alarm
Low
alarm
Process
values Counter
Current output
Priority
Error te
xt
Q
m
[%, unit]
Qv [
%
, un
it]
Density [g/cm
3
]
Te
mpe
ra
tu
re [
°C]
C
once
ntration [
%
]
N
et m
ass fl
ow
Standard density
g/cm
3
]
Stan
dard vo
lu
me
[2
0 °C]
All c
ou
nt
ers
98
No Frontend Board detected
0
0
1
20
0
0
1
0
–
96
DSP Failure on Frontend Board.
0
0
1
–
0
0
1
0
–
94 Safety
Alarm
Curr.Out
31/32 – – – – – – – – –
–
93
Sensor amplitudeout of range.
0
0
1
–
0
0
1
0
–
92 FEB
voltages
outside
range. 0 0 0 0 0 0 0 0 0
91 MB
voltages
outside
range. – – – – – – – – –
90 Sensor temperature measure error
1) 1) 1) 20 1) 1) 1) 1) –
88
FEB communication error. EMC
disturbance.
0 0 1 20 0 0 1 0 –
86 Curr.Out
31/32
com
error. – – – – – – – – –
CO1
only
84
NV data defect. Data storage
irreparable.
0 0 1 20 0 0 1 0 –
82
Incompatible Frontend Board.
0
0
1
20
0
0
1
0
–
80
Density
failure
0 0 1 20 0 0 1 0 –
78
Flowrate to zero
0
0
–
–
–
0
–
0
–
In accordance with process value
76
All
totalizer
stopp.
– – – – – – – –
–
74
Totalizer reset. Reset of one or
more Totalizer
– – – – – – – – 0
–
72
Simulation is on. Simulating
process/output value.
– – – – – – – – –
–
70 An
alarm
is
simulated.
– – – – – – – – –
65 CO 31/32 readbackcurrent deviates
– – – – – – – – –
< 3.3 mA
60
Sensor
driver
current
to
high. – – – – – – – – –
–