Menu / parameter
Description
Device Setup / ...Transmitter / ......Cut Off
Low Flow Cut Off
Sets the switching threshold for the low flow cut-off.
If the flow rate is below the switching threshold, there is no flow measurement. The setting of 0 % deactivates the low flow
cut-off.
Factory setting: 0.5 %
Low Flow Hysteresis
Sets the hysteresis for the low flow cut-off as it is defined in the parameter ‘Low Flow Cut Off’.
Factory setting: 20 %
Density Cut Off
Sets the low flow for density.
Factory setting: 0.2 g/cm³
Example:
With a set low flow of 0.5 %, the output is set to 0 as soon as the mass flow down-scales 0.5 % of Q
m
Max.
With a low flow hysteresis of 20 %, the actual value is issued again as soon as the mass flow up-scales 0.6 % of Q
m
Max.
Device Setup / ...Transmitter / ...Feature Settings
DensiMass On / Off
Indicates whether the DensiMass function is active.
DensiMass Code
Sets the device-specific code for activating the DensiMass function. To use this function subsequently, contact the ABB
service team or sales organization.
After entering the code, restart the device (e.g. using the parameter ‘Device Reset' or by briefly switching off the power
supply).
Batchflow On / Off
Indicates whether the FillMass function is active.
Batchflow Code
Sets the device-specific code for activating the FillMass function. To use this function subsequently, contact the ABB service
team or sales organization.
After entering the code, restart the device (e.g. using the parameter ‘Device Reset' or by briefly switching off the power
supply).
VeriMass On / Off
Indicates whether the VeriMass function is active.
VeriMass Code
Sets the device-specific code for activating the VeriMass function. To use this function subsequently, contact the ABB
service team or sales organization.
After entering the code, restart the device (e.g. using the parameter ‘Device Reset' or by briefly switching off the power
supply).
Menu / parameter
Description
Device Setup / ...System Zero
Manual Adjust
Sets the value for zero point adjustment in % of Q
max
DN
Auto Adjust
Starts the automatic zero point balancing using
. Automatic zero point balancing takes approx. 60 seconds.
NOTICE
Prior to starting the zero point adjustment, make sure that:
• There is no flow through the sensor (close all valves, shut-off devices etc.)
• The sensor must be filled completely with measuring medium for measurement.