…Functions
Bank Control
Bank control functionality enables a bank of output devices such as pumps, heaters
or fans to be scheduled
On
and
Off
under a duty / assist strategy.
If required, one of two different wear levelling schedules can be selected,
Rotate
or
FIFO
(
First In First Out
).
Up to 6 stages may be configured for bank control, each of which can be assigned to
a relay or digital output. Each stage has an associated
On
trip value,
Off
trip value and
initial
Output
. All stages included in a wear levelling schedule must use the same
schedule type (
Rotate
or
FIFO
).
The example (overleaf) illustrates how the two modes operate to achieve wear levelling
of 3 pumps in a duty / assist strategy.