![background image](http://html.mh-extra.com/html/abb/controlmaster-cm15/controlmaster-cm15_user-manual_2340054.webp)
ControlMaster CM15 and CMF160
Universal process indicator
1
/
8
DIN
7 Advanced Level
52
IM/CM/I–EN Rev. P
…Process Alarm
Alarm 1 (8)
Type
Alarm types comprise: High Process, Low Process, High Latch, Low Latch.
Tag
The alarm
Tag
is displayed as a diagnostic message and appears in the
Diagnostic Status
Bar
and the Diagnostic view in the
Operator Level
.
S
ource
The analog source –see Appendix A.2, page 95 for description of sources.
Trip
The alarm trip level in engineering units – see page 99 for unit options.
High and Low Latch Alarm Action
Trip
Point
Alarm On
Alarm
Off
Hysteresis
Process
Variable
Alarm Latched
Alarm Acknowledged by Operator
Alarm Acknowledged by Operator
Alarm
Off
Trip
Point
Alarm On
Hysteresis
Alarm
Latched
Process Variable
High Latch Alarm
Low Latch Alarm