![background image](http://html.mh-extra.com/html/abb/controlmaster-cm15/controlmaster-cm15_user-manual_2340048.webp)
ControlMaster CM15 and CMF160
Universal process indicator
1
/
8
DIN
7 Advanced Level
46
IM/CM/I–EN Rev. P
… Input/Output / …Analog Input 1 (4)
Eng Units
The selected units are used by the linearizer and displayed in the
Operator
pages.
Not applicable for:
Pulse Input
,
Digital volt-free
and
24V Digital
parameters.
Thermocouple
and
RTD
inputs (see page 44) are restricted to
deg C
,
deg F
,
Kelvin
–
see Appendix C, page 99 for analog input (engineering) units.
Eng. Dps
Engineering decimal places – selects the resolution required to be displayed for the input
value.
Eng. Low
Eng High
Specifies the engineering low (minimum) / high (maximum) value.
For example, for an electrical input range of 4.0 to 20.0 mA, representing a pressure
range of 50 to 250 bar, set the
Eng Low
value to 50.0 and the
Eng High
value to 250.0.
Not applicable for
Pulse Input
– see page 44.
Pulse Units
Selects the unit of measure for the pulse input type.
Pulse / Unit
Sets the number of pulses required to represent 1 pulse unit (as set above).
For example, if
Pulse Units
= Kl and
Pulse / Unit
= 10.00000000, each pulse represents
0.1 Kl, 10 pulses = 1 Kl.