ControlMaster CM15 and CMF160
Universal process indicator
1
/
8
DIN
10 Specification
IM/CM/I–EN Rev. P
87
Math blocks*
Number:
8
Operators:
+, –, x, /
Average, Maximum, Minimum
High / Low / Median select
Square root
Multiplexer
Delay timers*
Number
2
Programmable
Delay
Duration
Logic equations*
Number
8
Elements
15 per equation
Operators
OR, AND, NOR, NAND, NOT, EXOR
Custom linearizer*
Number
2
Elements
20 breakpoints
Bank control*
Number of outputs
6
Wear levelling
Rotate or FIFO
Totalizer
Number **
Up to 2
Type:
Analog, digital, frequency or pulse
Statistical calculations:
Average, maximum, minimum (for analog signals)
Update rate:
125 ms
*
Functionality level 'Standard' and above only
**
Single totalizer available with base functionality, dual totalizers