ControlMaster CM15 and CMF160
Universal process indicator
1
/
8
DIN
7 Advanced Level
IM/CM/I–EN Rev. P
45
… Input/Output / …Analog Input 1 (4)
Elect. Low
Sets the required electrical range.
Note
. Applicable only to
Millivolts, Milliamps, Volts
and
Ohms
.
Linear Inputs
Standard Analog Input
Accuracy (% of
Reading)
Millivolts
0 to 150 mV
0.1 % or ±20 µV
Milliamps
0 to 45 mA
0.2 % or ±10 µA
Volts
0 to 25 V
0.2 % or ±20 mV
Resistance
(low)
0 to 550
0.2 % or ±1
Resistance
(high)
0 to 10 k
0.1 % or ±5
Elect. High
Sets the required electrical range.
Note
. Applicable only to
Millivolts, Milliamps, Volts
and
Freq. Input
.
Linearizer
Selects the linearizer type required to condition the input signal.
Notes
. For thermocouple applications using an external fixed cold junction, set
Input
Type
to
Millivolts
(see page 44) and select the appropriate linearizer type.
Not applicable for
Pulse Input
,
Digital volt-free
,
24V Digital
parameters – see page 44.