Increment Segment Time
Decrement Segment Time
NO
PG.SL
r.16
Segment Time Increment Source (Current Segment)
The time of the current segment can be increased (by an amount set
in the Segment Time Adjust frame) each time the source is activated.
(ie. the source is leading edge triggered).
See Rear Fold-out/Table C,
Digital Sources.
Segment Time Decrement Source (Current Segment)
The time of the current segment can be decreased (by an amount set
in the Segment Time Adjust frame) each time the source is activated.
(ie. the source is leading edge triggered).
See Rear Fold-out/Table C,
Digital Sources.
Segment Time Adjust Value (Current Segment)
The value set is added to or subtracted from the remaining time of a
running segment via a digital signal or from front panel keys, when in the
Time Remaining in Current Segment
frame of the
Operating Page
.
[0.1 to 100.0 or '
OFF
']
The time units are set in the
Time Units
frame. If
OFF
is selected, this
function is disabled.
Front Panel Run/Hold Enable
YES
–
Enabled
NO
–
Disabled
Front Panel Stop Key Enable
YES
–
Enabled
NO
–
Disabled
Front Panel Program Select Enable
YES
– Operator level program select enabled
NO
– Operator level program select disabled
Continued…
3
PROFILES…
r.11...r.16
…3.4
Ramp/Soak Profile Control
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.