86
…5
CONFIGURATION MODE
…5.6
Level A – Control Configuration
Configured Output 1
The control output value required when manual is selected by manual
mode source 1.
[0 to 100% or '
LASt
' (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Manual Mode Selection Source 2
The digital source required to select manual mode and Configured
Output 2.
See Rear Fold-out/ Table C
– Digital Sources.
Configured Output 2
The control output value required when manual is selected by manual
mode source 2.
[0 to 100% or '
LASt
' (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Auto/Manual Selection Source
Used with auto/manual station.
The source required to lock into manual mode with Configured Output 3.
Switching from manual to auto is not possible via the front panel.
See Rear Fold-out/ Table C
– Digital Sources.
Note. If template 3 is selected, the source is assigned to alarm 1. If
template 4 is selected, the source is assigned to digital input 1.
Configured Output 3
The control output value required when manual mode is selected by the
auto/manual selection source.
[0 to 100% or '
LASt
' (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Continued…
A.13...A.17
•1
Digital inputs are active when a volt-free contact is closed or a low TTL signal is applied
OFF
AM.5r
0.0
COP.3
A.16
A.17
0.0
C.OP2
A..15
OFF
M5r2
A..14
0.0
C.OP1
A.13
Auto
Manual with output =
C.OP3
•1
Auto
Auto
Manual with output =
C.OP2
•1