Status codes
4.3.
Introduction
4.3.1.
The following status codes are defined for the IEC 60870-5-104 master protocol. Some
typical reasons for some of the status codes are also given.
Link layer status codes
4.3.2.
ITCP_REMOTE_HOST_CONTINUOUSLY_BUSY. Not used at the moment.
17800
ITCP_LINE_INITIALISING. Line status value before the initialisation of the TCP
interface for the protocol is completed.
17801
ITCP_LINE_INITIALISATION_FAILED. Line status value when the initialisation
of the TCP interface failed.
17802
ITCP_REMOTE_HOST_BUSY. Device status is set to this value when the data
transfer is disabled due to received ‘stopdt’ frame.
17803
ITCP_REMOTE_HOST_NOT_RESPONDING. Device status is set to this value
when the connection to a remote host is not established.
17804
ITCP_LINE_NOT_CONNECTED. Line status is set to this value when there is
no connection to any configured host.
17805
ITCP_LINE_STOPPED. Line status value when the line is taken out of use.
17806
ITCP_RECEIVER_OUT_OF_BUFFERS. Internal error situation.
17807
ITCP_REMOTE_HOST_NOT_READY. Returned to SCIL in case there is no
connection to the host.
17808
ITPC_ILLEGAL_ATTRIBUTE_VALUE. Returned to SCIL when the attribute value
given is out of range.
17820
Application layer status codes
4.3.3.
ICCC_INVALID_ATTRIBUTE_VALUE. The value set to an attribute of an IEC
station is incorrect, for example, one of the elements of the vector written to the
SD attribute is out of range.
13851
ICCC_INVALID_INDEX_RANGE. The index range used when accessing an
attribute of an IEC station is incorrect.
13852
ICCC_INVALID_ATTRIBUTE. The STA object attribute used is not valid for the
IEC slave protocol.
13853
ICCC_ASDU_TABLE_NOT_CREATED. Internal software error.
13854
ICCC_UNKNOWN_ASDU_NAME. The name of the ASDU written to the SD or
EV attribute is not supported.
13855
ICCC_ASDU_QUEUE_FULL. No more events can be written to one of the queues
by using the SD or EV attribute since the queue is full.
13856