Supported
Description
Function
Code
Yes
Set the output directly
Respond with status of control point
Direct operate
5
Yes
Set the output directly
No respond
Direct operate - no
ack
6
Freeze Function Codes
Yes
Copy the specified objects to freeze buffer
Respond with status of operation
Immediate Freeze
7
Yes
Copy the specified objects to freeze buffer
No respond
Immediate Freeze
-no ack
8
Yes
Copy the specified objects to freeze buffer and clear objects
Respond with status of operation
Freeze and Clear
9
Yes
Copy the specified objects to freeze buffer and clear objects
No respond
Freeze and Clear -
no ack
10
No
Copy the specified objects to freeze buffer at specified time
Respond with status of operation
Freeze with time
11
No
Copy the specified objects to freeze buffer at specified time
No respond
Freeze with time -
no ack
12
Application Control Function Codes
Cold Restart Per-
form the desired
reset sequence
Respond with a
time object Yes
13
Yes
Perform the desired partial reset operation
Respond with a time object
Warm Restart
14
No
Initialise the specified data to default
Respond with the status of operation
Initialise Data to
Defaults
15
No
Prepare the specified application to run
Respond with the status of operation
Initialise Application
16
No
Start the specified application to run
Respond with the status of operation
Start Application
17
No
Stop the specified application to run
Respond with the status of operation
Stop Application
18
Configuration Function Codes
150
1MRS758690
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual