IEC 104 OPC server
4.
About this section
4.1.
This section provides reference information about the following issues:
•
IEC 61850 data modeling
•
Attributes
•
Status codes
IEC 61850 data modeling
4.2.
General information about IEC 61850 data modeling
4.2.1.
The relationship between the IEC 61850 data modeling and IEC104 OPC Server is
described in this section.
For each data class, there is a table giving a detailed description about the relation between
the IEC104 data and IEC 61850 data object attributes and services. The tables also
describe how the data is presented on the OPC Server name space.
The columns in the tables have the following content types:
•
Name specifies the OPC item name of the attribute/service.
•
Type specifies the IEC 61850 type of the attribute.
•
Value/ Value range specifies the allowed values and ranges of the attribute/service.
•
Mandatory/Optional specifies whether the attribute is considered as mandatory or
optional according to the IEC 61850 standard.
•
IEC104 information element specifies the IEC104 information element related to
the attribute/service.
•
OPC data types specify the OPC data type used for the OPC item.
Single point status (SPS)
4.2.2.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/Value range
Type
Name
VT_BOOL
SPI(0=ON, 1=OFF)
M
TRUE | FALSE
BOOLEAN
stVal
VT_I4
BL, SB, NT, IV
M
Quality
q
VT_DATE
CP24Time2a
CP56Time2a
M
TimeStamp
t
89
COM600 series 5.0
1MRS758690
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Summary of Contents for COM600 series 5.0
Page 1: ... COM600 series 5 0 Master Protocols Ethernet and Applications Technical Reference Manual ...
Page 2: ......
Page 8: ...8 ...
Page 156: ...156 ...
Page 163: ......