Maximum range of values for all the time-outs: 1 seconds to
255 seconds , accuracy 1 s.
Maximum number of outstanding I format APDUs (k) and the latest
acknowledgment (w)
Selected value
Remarks
Default value
Parameter
1-32767 s
Maximum difference
receive sequence
number to send state
variable
12 APDU
k
1-32767 s
Latest acknowledg-
ment after receiving w
I-format APDUs
8 APDUs
w
Maximum range of values k: 1 to 32767 (215-1) APDUs, accuracy 1 APDU.
Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU
(Recommendation: w should not exceed 2/3 of k).
Port number
Remarks
Default value
Parameter
In all cases
2404
Port number
RFC 2200 suite
RFC 2200 is an official Internet standard which describes the state of standardization of
protocols used on the Internet as determined by the Internet Architecture Board (IAB).
It offers a broad spectrum of actual standards used in the Internet. The suitable selection
of documents from RFC 2200 defined in this standard for given projects must be chosen
by the user of this standard.
Ethernet 802.3
Serial X.21 interface
Other selection RFC 2200:
List of valid documents from RFC 2200
145
COM600 series 5.0
1MRS758690
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual